Products


CFS-30

KAYDON / CLEAN FUEL, INC. - CFS-30 – DIESEL ENGINE FUEL RELIABILITY SYSTEM
 
 
 
 

 

Specifications

Size
32”L x 24”W x 48”H (each cabinet - 2 required)
Weight
700 pounds
Inlet Connections
2" NPT
Outlet Connections
1-1/2" NPT
Strainer Mesh
100
Pump
30 gpm positive displacement gear pump (cast iron) – NPSHR = 12.0 feet
Coalescer Element
C220047
Separator Element
608061
Materials of Construction Aluminum and Carbon Steel Construction
Maximum Allowable Working Pressure 150 PSI
Controls Interface Touch Pad with Display Screen
System Fault Alarms High Water Level in filter vessel, High Water Level in water collection drum, High element differential pressure, High pump vacuum, System Fault Alarm Horn for high water level in water collection drum and basin and Differential Pressure Gauge/Switch (to indicate need for coalescer replacement).
Operating Voltage/Amp Draw 120 VAC, single phase, 18.0 full load amp at 120 VAC
System Guages & Indicators Differential Pressure Gauge & Switch (0-40 psid, element change out = 15 psid)
Automatic Water Drain Automatic Water Drain Assembly
Code Construction N/A
Performance Water removal down to 50 ppm total water, with an influent of 5,000 ppm or less
Available Options
  • Remote Start/Stop
  • 220 VAC / 1 PH / 60 Hz
  • Heat Tape and Temperature Sensor (Keeps water from freezing)
  • Veeder Root Fuel Level Sensing Input
  •  Algae - X
  • Remote Pump
  • Multi-Tank Manifold 


Ordering Information

Product Number: 4XLDa-000097U
Size: 1 1/2", 3/4"

Spare Parts
• Coalescer Element
• Separator Element
• O-Ring Part